コンクリートの気泡組織に影響する要因と耐凍害性に関する研究
|
著者 |
濱 幸雄
平野 彰彦
田畑 雅幸
|
収録物名 |
日本建築学会構造系論文集
|
巻 | 73 |
号 | 634 |
開始ページ | 2061 |
終了ページ | 2067 |
収録物識別子 |
ISSN 13404202
|
内容記述 |
その他
The influence of various factors such as chemical admixture and mixing conditions on the air void system of concrete was investigated by the buoyancy method. When AE agent was used independently, the difference of quantity and quality of entrained air due to the type of AE agent was not recognized among 10 types of AE agent used in this study. However, when AE agent was used with superplasticizer, we could see big difference in air entraining due to the type of AE agent. Furthermore, the influence of mixing efficiency and grading of sand was also large besides AE agent. It was possible to control frost resistance by the appropriate quantity and quality of entrained air even if concrete was subjected to wetting/drying cycles. The section air quantity of diameter from 100 to 500 micrometer is especially effective to prevent frost damage of concrete.
|